Elangcompressor Logo

Basic Knowledge

Home » News » Basic Knowledge

Basic Knowledge

SCFM vs CFM Explained

Time: 2025-11-12

Standard cubic feet per minute (SCFM) and cubic feet per minute (CFM) are both units used to calculate or measure air flow rates. SCFM and CFM are calculated differently and are commonly employed within the air compressor industry. This article explains the distinction between them, details the conversion between SCFM and CFM, and provides a brief explanation of ACFM.

scfm vs cfm

Definition of: SCFM vs CFM

SCFM(Standard Cubic Feet per Minute):

1. “Standard” air flow rate in cubic feet per minute.

2. Measurement conditions: will be measured in a standard state, such as fixed temperature, humidity and pressure as a standard state.

3. An example of a commonly used US standard (with minor variations):
Temperature 68°F (20°C): close to the global average room temperature, excluding the effects of thermal expansion and contraction.
Humidity 0%: eliminates water vapor interference with air density
Pressure 14.7 psi: Standard atmospheric pressure at sea level to establish a uniform datum
Note: ISO standard is 15°C/0% RH, industry needs to specify the standard used.

CFM(Cubic Feet per Minute):

1. how many cubic feet of air flow per minute

2. There is no specification on what temperature, humidity and pressure to measure under.

3. So the same air compressor in different conditions measured CFM results will have a big difference

Conversion: SCFM and CFM

convert-scfm to cfm

Assuming that the same Elang air compressor is used under different conditions:
Measured CFM = 110 in summer (high temperature and low pressure)
Converted from the standard condition, probably SCFM = 100
CFM > SCFM, which means that the actual air density in the measurement environment is lower than the standard density.

Pressure (psig)Temperature (°F)Conversion Factor (SCFM per CFM)SCFM (for 100 CFM)
30 60 3.088 308.8 (CFM to SCFM)
30 70 3.029 302.9 (CFM to SCFM)
30 80 2.973 297.3 (CFM to SCFM)
30 90 2.919 291.9 (CFM to SCFM)
30 100 2.867 286.7 (CFM to SCFM)
40 60 3.778 377.8 (CFM to SCFM)
40 70 3.707 370.7 (CFM to SCFM)
40 80 3.638 363.8 (CFM to SCFM)
40 90 3.572 357.2 (CFM to SCFM)
40 100 3.508 350.8 (CFM to SCFM)
50 60 4.469 446.9 (CFM to SCFM)
50 70 4.385 438.5 (CFM to SCFM)
50 80 4.304 430.4 (CFM to SCFM)
50 90 4.225 422.5 (CFM to SCFM)
50 100 4.15 415.0 (CFM to SCFM)
60 60 5.16 516.0 (CFM to SCFM)
60 70 5.062 506.2 (CFM to SCFM)
60 80 4.969 496.9 (CFM to SCFM)
60 90 4.878 487.8 (CFM to SCFM)
60 100 4.791 479.1 (CFM to SCFM)
70 60 5.851 585.1 (CFM to SCFM)
70 70 5.74 574.0 (CFM to SCFM)
70 80 5.634 563.4 (CFM to SCFM)
70 90 5.531 553.1 (CFM to SCFM)
70 100 5.433 543.3 (CFM to SCFM)
80 60 6.541 654.1 (CFM to SCFM)
80 70 6.418 641.8 (CFM to SCFM)
80 80 6.299 629.9 (CFM to SCFM)
80 90 6.184 618.4 (CFM to SCFM)
80 100 6.074 607.4 (CFM to SCFM)
90 60 7.232 723.2 (CFM to SCFM)
90 70 7.096 709.6 (CFM to SCFM)
90 80 6.964 696.4 (CFM to SCFM)
90 90 6.838 683.8 (CFM to SCFM)
90 100 6.715 671.5 (CFM to SCFM)
100 60 7.923 792.3 (CFM to SCFM)
100 70 7.773 777.3 (CFM to SCFM)
100 80 7.629 762.9 (CFM to SCFM)
100 90 7.491 749.1 (CFM to SCFM)
100 100 7.357 735.7 (CFM to SCFM)

SCFM vs CFM vs m3/min

1 scfm ≈ 1.1199 cfm

1 scfm ≈ 0.8478 m3/min

Special unit conversions:

1 l/min 0.0353 cfm

1 l/min ≈ 0.0299 scfm

1 l/s ≈ 2.1189 cfm

1 l/s ≈ 1.7992 scfm

Meaning: CFM and SCFM vs ACFM

CFM: only tells the volume flow rate, regardless of the thinness and density of the air
SCFM: has been corrected for environmental differences, easy to compare between different machines and countries
ACFM (actual CFM): the flow rate in the actual use of the environment, closer to the real working performance.